Kitchen Split Receptacle Circuits

Author:  Terry Peterman      What exactly is a kitchen split receptacle circuit, and why the confusion with this common household wiring configuration?  I received an e-mail from a website visitor who was wondering if there was a problem with a counter outlet in her home.   I answer her question in the following video, article and wiring diagram below:

Question Regarding a Kitchen Split Receptacle Circuit:

Q: We have an electrical outlet that has 240 to one plug and the other plug has 120.  There are three wires involved in this counter top plug; red white and black.

Red plus white = 120 volts

White plus black = 120 volts

Black and red = 240 volts!  Ouch!

Any idea on how to fix?  – Trish

 

 

Understanding the Kitchen Split Receptacle Circuit:

Trish, what you have is actually a perfectly normal situation which meets the code rules in many electrical jurisdictions.  This is what is known as a split receptacle kitchen circuit.

It is fed by a 2-pole, 15A circuit breaker, and uses 14/2 cable.  In this situation, the neutral is shared between the two hot wires (red and black) that come from the panel.

You are correct in that you do have 240V between the black and the red conductors.  However, the receptacle is wired so as to only have 120V in each half of the duplex receptacle, and the brass tab is broken between the top and the bottom half of the receptacle on the hot (brass) side of the device, but remains intact on the neutral side.  This way the two circuits that feed this outlet “share” the neutral connection.

Kitchen Split Receptacle Circuits

Kitchen Split Receptacle Circuit Wiring Diagram:

Kitchen Split Receptacle Circuit

Because the two circuits are from opposite sides of the panel, the neutral will only carry the unbalance load.  So if you are using a toaster plugged into the top half, and it is using 8A on circuit #1, and the coffee maker plugged into the bottom half using 6 amps, then the neutral will only be carrying 2 amps of current back to the panel.  The maximum that the neutral conductor will carry on a circuit like this is the maximum that one of the appliances that are plugged in will draw.

The new code now requires all kitchen receptacles to be protected by ground fault circuit interrupter (GFCI) receptacles, and must have at least two 20A circuits supplying general purpose kitchen receptacles.

 

Split kitchen receptacles are still quite common, and are still allowed in some jurisdictions.  However, where the new code rules have been adopted, the existing installations are grandfathered and are not and will not be mandated to be rewired.  I personally like the kitchen 3-wire circuits as I think they offer more flexibility on counter top appliance locations and configurations with plenty of capacity to supply the various power requirements.  However, the complicating issue and change motivating factor was the requirement for GFCI protected outlets in the kitchen area, and protection of split circuitry is more complicated and more expensive to achieve than using 20A GFCI receptacles with feed-through capability.

Not sure about tackling this yourself? Remember: Can’t do it yourself? Get help from a qualified electrical contractor/

This entry was posted in Q & A, Receptacles, Wiring-Videos and tagged , , , , , , , . Bookmark the permalink.
  • Clintdm

    Very well stated and explained Terry.

  • Djdrummerb1983

    dont understand how wire coming in could be 14/2 not 14/3 with 2 hots(black & red split to phase A and phase B buses at the panel) and a common, plus of course ground? if i am way off please explain.

    • Terry

      Good catch!  Typo!  Should have said 14/3, not 14/2.  Seems it doesn’t matter how many times you proof read, mistakes can still slip by.  Thanks for pointing it out.  We will fix this right away.

  • Confused

    We have a split receptacle that only has one 14/3 wire coming in. The next receptacle only has one 14/2 wire coming in but somehow will only function if something is plugged into the 14/3 receptacle.???? I’m assuming there is a hidden junction box somewhere where these two join but what kind of wiring mess would have to happen for a plug to work only when another is in use?

  • Bulldog51

    I am trying to install a new Leviton T5630 into a receptacle box that was previously wired with a Split Receptacle. The T5630 only has one positive and one negative contact. What do I do with the extra wire?

    • Internetelectrician

      You can just cap it off with a wire nut and tuck it in to the back of the box.

  • RCDC13

    Hey guys, I am in Victoria BC, and I am trying to find a rising duplex plug in s/s rated to be on a Island Countertop,but am not finding anything. Do we have to have a plug on an island or has that code changed? My client wants a plug but has that code changed?

 

The Basics of Household Wiring DVD

"If you're looking for a good reference to help you understand simple home wiring, I personally recommend 'The Basics of Household Wiring' DVD".

Terry Peterman, the Internet Electrician
 
Electrical Wiring
Electrical Diagrams
Projects
How To
Electrical Tools
Electrical Videos
Copyright © www.electrical-online.com |  LEGAL DISCLAIMER |  PRIVACY POLICY